Product description 
  3.4 Mechanical operating mechanisms 
3VL molded-case circuit breakers 
System Manual, 03/2009, 110 0110 - 02 DS 01 
23 
3.4  Mechanical operating mechanisms 
3.4.1  Toggle handle operating mechanism 
In the basic version, the SENTRON VL circuit breakers have a toggle handle as an operating 
mechanism. This also functions as an indicator of the switching position. The "Tripped" 
position is also displayed in addition to the "ON" and "OFF" positions. 
The toggle handle goes to the "tripped" position when the internal trip mechanism is 
activated by an overcurrent situation, e.g. overload or short-circuit. 
Activation by an undervoltage release or shunt release will also cause the toggle handle to 
move to the "Tripped" position. 
 
 
Toggle handle in the "ON" 
position 
The toggle handle must be returned to the 
"OFF/RESET" position before the circuit breaker can be 
turned back on again. This enables the internal release 
mechanism to be reset. SENTRON VL circuit breakers 
with toggle handle operation comply with the "Network 
disconnecting device" condition (5.3.2 Section c) and 
5.3.3) according to DIN EN 60204-1 (VDE 0113-1). 
Toggle handle positions 
 
ON  OFF 
RESET 
Tripped 
 
Toggle handle positions