3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
83
Installing/mounting
7
7.1 Installation methods
Installation overview
The SENTRON VL circuit breakers are available in fixed-mounted, plug-in or withdrawable
versions, with three or four poles.
Table 7- 1 Overview of installation methods
Circuit breaker type Fixed Plug-in Withdrawable part
VL 160X x x -
VL 160 x x x
VL 250 x x x
VL 400 x x x
VL 630 x x x
VL 800 x - x
VL 1250 x - x
VL 1600 x - x
Fixed mounting
Mounting plate connection
SENTRON VL circuit breakers can be installed direct onto the mounting plate. If busbars or
terminals are used to connect the circuit breaker on the back of the mounting plate, the
appropriate safety clearances must be observed (see technical overview)