Technical data 
  12.19 IP degrees of protection 
3VL molded-case circuit breakers 
System Manual, 03/2009, 110 0110 - 02 DS 01 
189 
12.19  IP degrees of protection 
All SENTRON VL molded-case circuit breakers are constructed with degree of protection 
IP20 regardless of size and version. 
A wide range of additional accessories is also available for the basic version of the 
SENTRON VL circuit breaker in IP20. 
The accessories listed below are designed to provide a higher degree of protection: 
The degree of protection in accordance with IEC 60529 is listed in the table below: 
Table 12- 53  Overview of degrees of protection 
Circuit breaker  Protection  Degree of 
protection
 
Circuit breaker  
Finger-proof  
Protected against solid foreign bodies with a diameter 
of 12.5 mm or larger. 
IP20 
 
Circuit breaker with terminal cover 
Protected against access to live parts with a tool. 
Protected against solid foreign bodies with a diameter 
of 2.5 mm or larger. 
IP30 
 
Plug-in circuit breaker 
Finger-proof Protected against solid foreign bodies 
with a diameter of 12.5 mm or larger.  
IP20 
IP30
1)
 
 
Circuit breaker with cover frame and motorized 
operating mechanism 
Protected against access to live parts with a wire. 
Protected against solid foreign bodies with a diameter 
of 1.0 mm or larger. 
IP40
2)
 
 
Circuit breaker with cover frame for door cutout 
Protected against access to live parts with a wire. 
Protected against solid foreign bodies with a diameter 
of 1.0 mm or larger. 
IP40
2)
 
 
Circuit breaker with cover frame and rotary operating 
mechanism on front 
Protected against access to live parts with a wire. 
Protected against solid foreign bodies with a diameter 
of 1.0 mm or larger. 
IP40
2)
 
 
Circuit breaker with door coupling rotary operating 
mechanism 
Protected against ingress of dust and water jets from 
any direction. 
IP65
2)
 
1) 
  If the circuit breaker is installed and the supplied covers are mounted. 
2) 
  Depending on the degree of protection of the housing