3VL molded-case circuit breakers 
System Manual, 03/2009, 110 0110 - 02 DS 01 
41 
Functions 
5
5.1  Current protection 
5.1.1  Overcurrent trip unit 
The SENTRON VL circuit breakers are designed on the principle of magnetic repulsion of 
the contacts. The contacts open before the expected peak-value of the short-circuit current is 
reached. Magnetic repulsion of the contacts very significantly reduces the thermal load I
2
t as 
well as the mechanical load resulting from the impulse short-circuit current IP of the system 
components that occur during a short-circuit. 
 
(1)  Main connections  
(2)  Breaker mechanism 
(3)  Overcurrent trip unit  
(4)  Movable contact arm 
(5)  Arc chute 
(6)  Enclosure 
Figure 5-1  Interior view MCCB