3.3  Configuration 
3.3.1  Functional principle 
Design - mechanical principle 
All SENTRON VL circuit breakers have a trip-free mechanism that ensures the trip process 
is not prevented even if the operating mechanism is blocked or manually held in the "ON" 
position.  
The contacts are opened and closed by a toggle handle positioned in the center. This is 
attached to the front side on all circuit breakers. 
All SENTRON VL circuit breakers are "joint trip units". This means all contacts open or close 
simultaneously when the circuit breaker toggle handle is moved from "OFF" to "ON" or from 
"ON" to "OFF", or when the tripping mechanism is activated by an overcurrent or with the 
help of an auxiliary trip (shunt release or undervoltage release). 
Current limiting 
The SENTRON VL circuit breakers are designed on the principle of magnetic repulsion of 
the contacts. The contacts open before the expected peak-value of the short-circuit current is 
reached. Magnetic repulsion of the contacts very significantly reduces the thermal load I
2
t as 
well as the mechanical load resulting from the impulse short-circuit current I
P
 of the system 
components that occur during a short-circuit. 
You can find more information in Chapter 
Use in the motor protection area (Page 74). 
3.3.2  Subdivision according to power ranges 
VL160X circuit breakers 
The most important components of the VL160X circuit breakers are the three current paths 
with the incoming and outgoing terminals. The fixed and movable contacts are arranged in 
such a way as to guarantee magnetic repulsion of the contacts. In conjunction with the arc 
splitter chambers, a dynamic impedance is created that causes a current limitation through 
the reduction in the harmful effects of I
2
t and the I
p
 energy resulting from short-circuits.  
The overcurrent trip unit is a thermomagnetic device installed at the factory. It is equipped 
with fixed or adjustable overload releases and a fixed short-circuit release in each pole. 
To the right and left of the centrally positioned toggle handle of every SENTRON VL circuit 
breaker is a double-insulated accessories compartment for installing auxiliary switches or 
alarm switches as well as voltage and undervoltage releases.