Product description   
3.2 Application overview 
  3VL molded-case circuit breakers 
18  System Manual, 03/2009, 110 0110 - 02 DS 01 
3.2  Application overview 
The following overview shows the most frequently occurring applications 
Application overview 
 
Application  Type  Description 
 
3- and 4-pole circuit breakers 
VL160X 
VL160 
VL250 
VL400 
VL630 
VL800 
VL125 
VL1600 
Line protection 
The trip units for line protection are designed to protect cables and non-
motorized loads against overload and short-circuit. 
 
3-pole circuit breaker 
VL160 
VL250 
VL400 
VL630 
Motor/generator protection 
The overload and short-circuit releases are designed for optimum 
protection and direct-online starting of AC squirrel-cage motors. The 
circuit breakers for motor protection have phase-failure sensitivity and a 
thermal memory that protects the motor against overheating. The 
adjustable time lag class enables users to adjust the overload release 
to the startup conditions of the motor to be protected. 
 
3-pole circuit breaker 
VL160 
VL250 
VL400 
VL630 
Starter combination 
 Starter combinations consist of: Circuit breaker + contactor + overload 
relay. The circuit breaker handles short-circuit protection and the 
isolating function. The contactor has the task of switching the load 
feeder normally. The overload relay handles overload protection that 
can be specially matched to the motor. The circuit breaker for starter 
combination is therefore equipped with an adjustable and non-delayed 
short-circuit release. 
 
3- and 4-pole circuit breakers 
VL160X 
VL160 
VL250 
VL400 
VL630 
VL800 
VL1250 
VL1600 
Non-automatic air circuit breakers 
These circuit breakers are used as incoming circuit breakers, main 
switches or isolating switches without overload protection. They have 
fixed short-circuit releases so that back-up fuses are not necessary.