Technical data
12.1 Technical overview
3VL molded-case circuit breakers
146 System Manual, 03/2009, 110 0110 - 02 DS 01
Table 12- 2 Technical overview VL630 to VL1600
VL630 VL800 VL1250 VL1600
Rated current at 50 °C ambient
temperature
252 to 630 A 320 to 800 A 400 to 1250 A 640 to 1600 A
Rated operating voltage V
e
1)
(AC) 50-60 Hz [V]
690 690 690 690
Number of poles 3 4 3 4 3 4 3 4
(DC)
2)
[V] 600 600 -- -- -- -- -- --
$
%
'
&
mm A
mm B
mm C
mm D
190
279
106
138
253
279
106
138
190
406
119
151
253
406
119
151
229
406
157
207
305
406
157
207
229
406
15
207
305
406
152
207
Overcurrent trip unit
Thermomagnetic TM X X -- -- -- -- -- --
Electronic trip unit ETU
LCD
X X X X X X X X
Interchangeability X X X X X X X X
1)
Rated insulation voltage of the main conducting paths V
i
= 800 V AC
2)
Rated direct current data apply only for thermomagnetic overcurrent trip units. The values apply for at least 3 conductor
paths in series and extremely high switching capacity "L". For switching direct current, the maximum permissible direct
voltage per conductor path must be observed; see also "Suggested circuits for DC networks" in the Chapter "Application
planning".