Technical data
12.8 Motorized operating mechanisms
3VL molded-case circuit breakers
172 System Manual, 03/2009, 110 0110 - 02 DS 01
Table 12- 36 Stored-energy motorized operating mechanism for VL630 and VL800 or without stored energy for VL1250 and
VL1600
Type VL630 VL800 VL1250 VL1600
Synchronizable X X -- --
Operating range [V] 0,85 ... 1.1 U
S
0,85 ... 1.1 U
S
0,85 ... 1.1 U
S
0,85 ... 1.1 U
S
Minimum command duration at V
S
[ms] 50 50 50 50
Max. command duration
1)
[ms] Jog or pushbutton command
Total closing time [ms] <100 <100 <5000 <5000
Break time [s] <5 <5 <5 <5
Pause between ON and OFF command [s] >1 >1 >1 >1
Pause between OFF and ON command [s] >5 >5 >5 >5
Max. permissible switching frequency 1/h 60 60 30 30
Electrical data
Power consumption [VA] 250
50 .. 60 Hz
AC
[V] 48, 60, 110/127, 230/250 Rated control supply
voltage Vs
DC [V] 24, 48, 60, 110/127, 230/250
Fuse (time-lag "T"), DIAZED [A] 4 at 48V AC, 60V AC;
2 at 110/127V, 230/250V
Circuit breaker, C characteristic [A] 4 at 48V AC, 60V AC;
2 at 110/127V, 230/250V