System overview
4.2 Key data
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
39
Type VL160X
3VL1
VL160
3VL2
VL250
3VL3
VL400
VL4
VL630
3VL5
VL800
VL6
VL1250
3VL7
VL1600
3VL8
Stored-energy motorized operating mechanism (synchronization-enabled)
Power consumption [VA / W] < 100 < 100 < 100 < 200 < 250 < 250 - -
Rated control supply voltage V
s
[50 / 60 Hz V AC]
42-48 / 60 110-127 / 220-250 - -
Rated control supply voltage V
s
[V DC]
24 / 42-48 / 60 110-127 / 220-250 - -
DIAZED fuse
(performance class gG,
characteristic slow) [A]
4 2 - -
Miniature circuit breaker
(C characteristic in accordance
with DIN VDE 0641) [A]
4 2 - -
Operating range [V] 0.85 to
1.1 x V
s
0.85 to
1.1 x V
s
0.85 to
1.1 x V
s
0.85 to
1.1 x V
s
0.85 to
1.1 x V
s
0.85 to
1.1 x V
s
- -
Minimum command duration
with V
s
[ms]
50 50 50 50 50 50 - -
Max. command duration,
connection-dependent
1)
Jog/pushbutton or continuous command - -
Total closing time [ms] < 100 < 100 < 100 < 100 < 100 < 100 - -
Break time [s] < 5 < 5 < 5 < 5 < 5 < 5 - -
Pause between the commands
OFF and ON [s]
> 5 > 5 > 5 > 5 > 5 > 5 - -
Pause between the commands
ON and OFF [s]
> 1 > 1 > 1 > 1 > 1 > 1 - -
Max. permissible switching
frequency [1/h]
120 120 120 120 60 60 - -
x: Available
1)
Changeover contact also permissible, but note the pause times between ON and OFF.