4.3 Connection examples
PAC1020
32 Equipment Manual, 05/2020, L1V30610008B-01
3. 3-phase measurement, 3 conductors, unbalanced load, without voltage transformer,
with 3 current transformers
Connection type 3P3W
* The fuses are only used for cable protection.
All commercially available miniature circuit breakers up to 20 A (C) can be used.
**
Connection of supply voltage
*** Install a short-circuit device. Protection against overvoltage when the secondary transformer
circuit is open.
Figure 4-4 Connection type 3P3W, without voltage transformer, with 3 current transformers
4. 3-phase measurement, 3 conductors, unbalanced load, with voltage transformer, with
3 current transformers
Connection type 3P3W
* The fuses are only used for cable protection.
All commercially available miniature circuit breakers up to 20 A (C) can be used.
**
Connection of supply voltage
*** Install a short-circuit device. Protection against overvoltage when the secondary transformer
circuit is open.
Figure 4-5 Connection type 3P3W, with voltage transformer, with 3 current transformers