Appendix
A.1 Modbus
PAC1020
80 Equipment Manual, 05/2020, L1V30610008B-01
A.1.2 Exception codes
Overview
Table A- 2 Modbus exception codes
• The function code in the request is not a permis-
sible action for the slave.
• The slave is in a state in which it cannot process a
request of this type. This is the case, for example,
if it has not yet been configured and is requested
to return register values.
codes are supported.
dress
This address is not permissible for the slave. This is
the case, for example, if the combination of start
offset and transfer length is invalid.
number of registers.
The request contains a data value that is not permis-
sible for the slave. This indicates an error in the re-
maining structure of a complex request, e.g. an
offset and the specified
data length in the com-
mand are correct.
ure
Error in processing the data:
An indefinite error occurred when the slave attempt-
ed to execute the requested action.
offset and the specified
data length in the com-
A.1.3 Modbus measured variables with the function codes 0x03 and 0x04
Addressing the measured variables
You can use the Modbus function codes 0x03 and 0x04 on all the measured variables listed
below.
Error in the case of inconsistent access to measured values
Please ensure the start offset of the register is correct for
read access operations.
Please ensure the start offset and the number of registers are correct for
write access
.
If a value consists of two registers, a read command applied in the s
econd register, for
example, will generate an error code. The device will also output an error code if, for
example, a write operation ends in the middle of a multi-register value.