EasyManua.ls Logo

Siemens SENTRON PAC1020 - Applying the Measuring Voltage

Siemens SENTRON PAC1020
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection
4.3 Connection examples
PAC1020
34 Equipment Manual, 05/2020, L1V30610008B-01
6. 3-phase measurement, 3 conductors, unbalanced load, with voltage transformer, with
2 current transformers
Connection type 3P3W
* The fuses are only used for cable protection.
All commercially available miniature circuit breakers up to 20 A (C) can be used.
**
Connection of supply voltage
*** Install a short-circuit device. Protection against overvoltage when the secondary transformer
circuit is open.
Figure 4-7 Connection type 3P3W, with voltage transformer, with 2 current transformers
7. 2-phase measurement, 4 conductors, unbalanced load, without voltage transformer,
with 2 current transformers
Connection type 3P4W
* The fuses are only used for cable protection.
All commercially available miniature circuit breakers up to 20 A (C) can be used.
**
Connection of supply voltage
*** Install a short-circuit device. Protection against overvoltage when the secondary transformer
circuit is open.
Figure 4-8 Connection type 3P4W, without voltage transformer, with 2 current transformers
See also
Measuring inputs (Page 13)

Table of Contents

Related product manuals