Technical data
PAC1020
Equipment Manual, 05/2020, L1V30610008B-01
67
Digital input
Digital input
Number
1
Input voltage
Rated value
24 V DC
Maximum input voltage
30 V DC
Switching thresh. signal "1"
> 11 V DC
Input current
For "1" signal
Typ. 7 mA
Digital output
Digital output
Number
1
Design/function
Pulse output
Rated voltage
0 ... 30 V DC, typical 24 V DC (SELV or
PELV supply)
Output current
For "1" signal
Depends on the load and the external
power supply
Continuous load
50 mA (thermal overload protection)
Transient overload
130 mA for 100 ms
For "0" signal
0.2 mA
Internal resistance
55 Ω
Pulse output function
Standard for pulse emitter
Signal characteristics in accordance
with IEC 62053-31
Adjustable pulse duration
30 … 500 ms
Min. settable time frame
10 ms
Max. switching frequency
17 Hz
Short-circuit protection
Yes

Table of Contents