Commissioning
5.2 Setting the expansion module parameters
Expansion module I(N), I(Diff), analog
26 Manual, 04/2017, L1V30408520AG-01
Setting the ADC 0 - 20 mA parameters
LOWER LIMIT 0 – 9999 (specification of lower limit)
NEGATIVE ON/OFF (in the ON position, the lower limit is signed as a negative
number)
UPPER LIMIT 0 – 9999 (specification of upper limit)
NEGATIVE ON/OFF (in the ON position, the upper limit is signed as a negative
number)
UNIT DegC (degrees Celsius)
DegF (degrees Fahrenheit)
hPa (hectopascal)
% (percent)
" " (no unit)
◄ BACK Back to previous level
► SETTINGS Return to "SETTINGS" menu
Example:
A temperature measurement transmitter must be connected and parameterized at input I5.
Transmitter data:
Temperature range: - 50 ... + 250 °C
Output: 4 to 20 mA
The following parameters must be set at input I5:
1. Select ADC 4 - 20 mA
2. Enter I5 parameters
a. LOWER LIMIT 50
b. NEGATIVE ON
c. UPPER LIMIT 250
d. NEGATIVE OFF
e. UNIT DegC