Error Information for HMI FBs and System Messages
B-5
C7-613 Control System
A5E00138934-03
Error Code
(W#16#...)
RemedyCause
880A A selected process
screen/special screen or an info
text is not available.
Check whether a configuration is
available for the selected object. A
process screen or info text is configured
if at least one character is edited in the
static text.
A screen was selected in the
screen number range 128 to 255,
but the screen is not a special
screen.
Only the numbers 1 to 127 are valid for
the selection of process screens. In the
range of 128 to 255 only the screen
numbers of special screens (see Section
4.5.3) can be selected.
880B The selected process
screen/special screen cannot be
shown at the present time with
control job 51 (display image
selection).
A process screen/special screen cannot
be selected, if an object with a higher
display priority (refer to Section 5.8) is
currently being displayed.
Repeat the control job when the higher
priority object is no longer displayed.
Use the “OBJ_TYPE” parameter on the
“HMI API” FB to obtain the type of the
object that is currently being displayed
(refer to Section 4.5).