B-6
C7-613 Control System
A5E00138934-03
Error information of the “HMI EVENT” FB
Error
ID(W#16#...)
Cause Remedy
7000 Integrated HMI module of C7-613
is being initialized.
Incoming messages are delayed.
This is a status message that provides
information about the function that is
currently being performed. The
integrated HMI module of the C7-613 is
undergoing a cold restart. No additional
action is required.
The integrated HMI module of the
C7-613 can also be initialized during
operation, if an internal error occurs in
the integrated HMI module or during
basic HMI functions.
HMI functions are not possible during
initialization.
7001 Parameter assignment for the
integrated HMI module of the
C7-613 is underway.
Incoming messages are delayed.
The DBs with the configuration data
are being loaded from the MMC to the
internal memory of the integrated HMI
module. This always occurs following a
power ON or general reset, or when
the “Reload application” or “Swap
languages” system function is applied.
Wait until the parameter assignment is
completed.
The integrated HMI module of the
C7-613 can also be configured during
operation, if an internal error occurs in
the integrated HMI module or during
basic HMI functions.
HMI functions are not possible during
parameter assignment.
7002 Function for displaying a
message is being executed. Job
order has been placed.
This is a status message that provides
information about the function that is
currently being performed. No
additional action is required.
7003 A fault message was
acknowledged using the “Enter”
key. The acknowledgement bit is
set in the acknowledgement
area.
This is a status message that provides
information about the function that is
currently being performed. No
additional action is required.
7130 The job compartment is occupied
at the moment. Pending
messages will be delayed until
the job compartment becomes
free again.
This status is temporary. The job
request is repeated.
8211 The number specified in the
“API_DB” parameter is incorrect,
or the DB is not available.
Check to determine whether the
specified DB number is a valid DB
number for this CPU (1 to 511).
Check to determine whether it is the
instance DB of the “HMI-API” FB.
Check to determine whether the DB
exists at all.