Configuration
4.8 OPC UA
SIMATIC CC7
Operating Instructions, 10/2019, C79000-G8976-C503-02
69
Application name
Name of the OPC UA application of the gateway. The application name is required for
display of the OPC UA server at the clients.
Default:
SIMATIC Cloud Connect 7 OPC UA Server
Enable OPC UA server
Select the option to enable the OPC UA server function of the gateway.
Server address (IPv4) / (IPv6)
The IPv4 address and the IPv6 address, if available, of the cloud interface (P2) are
displayed in the two boxes.
Settings
Here you configure the server settings.
Port number
Here, you can change the port number of the server application. As default port number
4840 is used, the standard TCP port for the OPC UA binary protocol.
Permitted port numbers are as follows:
2000 .. 4499
4501 .. 34963
34965 .. 49151
Min. publishing interval (ms)
Here you set the minimum publishing interval that the server application of the gateway
should support. Lower values requested by OPC UA clients are not taken into account.
The OPC UA server provides the clients with the UA data in the cycle of the publishing
interval.
Range of values: 100 .. 65535 ms
Default setting: 500 ms
Min. sampling interval (ms)
Here you set the minimum sampling interval that the server application of the gateway
should support. Lower values requested by OPC UA clients are not taken into account.
The OPC UA server of the gateway samples its internal process image with the sampling
interval.
You specify reading from the station with the polling cycle, see section Station
configuration (Page 63).
The default is suitable for most applications. A smaller sampling interval can be selected
for reading fewer data points when the polling cycle is configured with a smaller value as
well.
Range of values: 100 .. 65535 ms
Default setting: 500 ms