EasyManua.ls Logo

Siemens SIMATIC CloudConnect CC7 Series - Cloud Configuration; Notes on Data Structuring and Configuration

Siemens SIMATIC CloudConnect CC7 Series
150 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration
4.9 Cloud configuration
SIMATIC CC7
Operating Instructions, 10/2019, C79000-G8976-C503-02
75
4.9 Cloud configuration
4.9.1 Notes on data structuring and configuration
WARNING
Writing values to outputs
Outputs and PLC tags
When referencing to outputs and PLC tags with write access, note that the values are
written immediately to the outputs of the CPU without first being processed by the user
program.
Writing values has a direct influence on the process.
DB tags
When referencing to DB tags, written values are only used when processed by the user
program.
Data structures
Depending on the cloud provider, the data is structured differently for transfer to the broker:
AWS / Azure / IBM Cloud
Topics
A topic is the channel for the transfer of values of one or more data points.
You can create several topics.
No groups can be configured.
MindConnect IoT Extension / Other Cloud
Groups
A group can contain one or multiple data points.
You can create one or more groups.
Topic
You can assign different topics to the groups.
MindConnect IoT Extension: In the default setting, the groups are assigned to the
standard topic "s/us" of the MindConnect IoT Extension.
Structure of the topic names
Because the requirements on the format of the topics can be different depending on the
receiver (broker, cloud), a topic name is made up of different parts.
Prefix and suffix generally apply to all topics.
Prefix and suffix are not relevant for groups.