Sinusoidal disturbance variables
The following tables show the electromagnetic compatibility of the ET 200SP HA distributed I/
O system to sinusoidal interference.
Table 9-3 HF radiation - sinusoidal interference
HF radiation according to IEC 61000-4-3/NAMUR NE21
Electromagnetic RF field, amplitude-modulated
Corresponds
to degree of
severity
80 MHz to 2.0 GHz 2.0 GHz to 6 GHz 3
10 V/m 3 V/m
80% AM (1 kHz)
Table 9-4 HF coupling - sinusoidal interference
RF coupling in accordance with IEC
61000-4-6
Corresponds to degree of severity
(10 kHz) 150 kHz to 80 MHz 3
10 V
rms
unmodulated
80% AM (1 kHz)
Table 9-5 Magnetic field IEC 61000-4-8
Magnetic field according to IEC
61000-4-8
Corresponds to degree of severity
50/60 Hz 100 A /m 5
50/60 Hz 1 kA/m for 1 s 5
Table 9-6 Voltage with power engineering frequency (line frequency)
Test according to IEC 61000-4-16 Corresponds to degree of severity
10 V 3
100 V for 1 s 3
Technical specifications
9.2 Electromagnetic compatibility
ET 200SP HA Distributed I/O system
System Manual, 08/2019, A5E39261167-AD 139