Pin assignment of the potential distributor
Table 4-9 Pin assignment of terminal blocks with a potential distributor (right side of terminal block: Terminals 33 to 64)
Terminal Assignment Terminal Assignment Explanations
33 L+ 34 L+ L+: Supply voltage L+, for sensors
3P2: Ground reference of the voltage bus 1P
4P2: Ground reference of the voltage bus 2P
5P2: Ground reference of the voltage bus 1P
6P2: Ground reference of the voltage bus 2P
35 L+ 36 L+
37 L+ 38 L+
39 L+ 40 L+
41 L+ 42 L+
43 L+ 44 L+
45 L+ 46 L+
47 L+ 48 L+
49 L+ 50 L+
51 L+ 52 L+
53 L+ 54 L+
55 L+ 56 L+
57 L+ 58 L+
59 L+ 60 L+
61 L+ 62 L+
63 L+ 64 L+
3P2 M 5P2 M
4P2 M 6P2 M
4.7.2.4 Terminal block with potential distributor (M potential)
General pin assignment with potential distributor
The pin assignment on the left side of the terminal blocks with a potential distributor should
be set in accordance with the configured I/O module.
36 M terminals are located on the right side of the potential distributor.
Note
Connection information
The M terminals on the right side are intended exclusively for the loads connected to the I/
O using 2-wire connection system. You may not use these terminals as the ground terminals
for other devices in the system.
Ensure that the total current does not exceed 10 A.
Plant planning
4.7 Configurations of the slots of I/O modules
ET 200SP HA Distributed I/O system
System Manual, 08/2019, A5E39261167-AD 41