EasyManua.ls Logo

Siemens SIMATIC ET 200SP HA - Page 88

Siemens SIMATIC ET 200SP HA
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
3
Push-in terminal
Spring release
Measuring tap
(suitable probes: Diameter 1.0 mm, cone height max 1.15 mm; length ≥ 10 mm in compliance
with the approved voltage category)
Holder for shield contact
P1 Supply voltage L+: The terminal assignment depends on the type of terminal block (see tables
in the following section "Supply voltage")
P2 Supply voltage M
Figure 6-6 View of the terminal block (example for the terminal block TB22-P32+4B/T)
Note
Specific designations of the process terminals in the wiring and block diagrams of the I/O
modules / terminal blocks
RES: Reserved, these process terminals must be left unconnected for future expansions
n.c.: Not connected, these process terminals have no function. However, they can be
connected to potentials specifically defined for a module, for example, for the laying unused
wires.
Supply voltage
Connect the supply voltage to a light-colored terminal block. The following two tables show the
terminal blocks to which you need to connect the cables of the supply voltage.
Table 6-3 Connection terminals for the supply voltage on the terminal block TB22.../ TB45-P32...
Potential Terminals on the terminal block Labeling of the terminal Voltage on the power
bus
Ground 1P2 and 2P2
Blue
P2
L+ 1P1 and 2P1
Note: Terminals connected
Red
P1
Wiring
6.5 Wiring the terminal block
ET 200SP HA Distributed I/O system
88 System Manual, 08/2019, A5E39261167-AD

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP HA

Related product manuals