Procedure
To connect the cable shield, follow these steps:
Table 6-5 Mounting the shield contact
Step Procedure Illustration
1 If necessary, connect the supply voltage L+ and M on the terminal
block.
Holder
Supply voltage L+, M
2 Press the shield contact up into the holder until you hear it click into
place.
Shield contact
Flat connector for push-on contact (6.3 × 0.8 mm)
3
Remove the cable insulation material around the shield terminal.
Connect the cable to the terminal block and insert the cable into
the shield contact.
Insulating material removed (approx. 20 mm)
Cable to sensor/actuator
Wiring
6.6 Connecting cable shields
ET 200SP HA Distributed I/O system
92 System Manual, 08/2019, A5E39261167-AD