Product overview
2.1 Properties
Interface module IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)
Manual, 10/2018, A5E03915895-AH
13
Properties
The module has the following technical properties:
Connects the ET 200SP distributed I/O system with PROFINET IO.
Power supply 1 L+ 24 V DC (SELV/PELV). The connection plug is included in the scope
of delivery of the interface module and is available as replacement part.
PROFINET IO connection via selectable BusAdapters
BA 2×RJ45 for RJ45 bus connector
BA 2×FC for direct connection of the bus cable
BA 2xLC for glass fiber-optic cable
BA 2xSCRJ for POF/PCF fiber-optic cable
BA SCRJ/RJ45 as media converter for POF/PCF fiber-optic cable ⇔ standard RJ45
connector
BA SCRJ/FC as media converter for POF/PCF fiber-optic cable ⇔ direct connection of
the bus cable
BA LC/RJ45 as media converter for glass fiber-optic cable ⇔ standard RJ45 connector
BA LC/FC as media converter for glass fiber-optic cable ⇔ direct connection of the
bus cable
Maximum configuration
64 ET 200SP I/O modules + 16 ET 200AL modules
1 m backplane bus (without interface and server module)
Maximum amount of I/O data
Gross data length (for input data and output data):
Without system redundancy S2:
1440 bytes
1440 bytes for shared device with 2 IOC (in total for both IOC)
360 bytes for shared device with more than 2 IOC (per IOC)
With system redundancy S2:
1000 bytes
360 bytes for system redundancy S2 and shared device with min. 1 additional IOC (per
IOC)
The number of maximum net data length for input data and output data depends on the
number and type of I/O modules used including ET 200AL modules.