Product overview
2.1 Properties
Interface module IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)
14 Manual, 10/2018, A5E03915895-AH
Net data length (for input data and output data):
The following minimum lengths can be applied without shared device and without explicit
calculation of the maximum net data length.
933 bytes without system redundancy S2
493 bytes with system redundancy S2
Calculation of the max. net data length:
Max. net data length = Max. gross length - number of I/O submodules (no user data, input or
output data) - number of I/O mixed modules (input and output data) - 5 bytes for interface
module and server module without ET-Connection (6 bytes for interface module with
ET-Connection)
The result of the calculation of the maximum net data length applies equally to input and
output data.
Accessories
You order the following accessories separately:
BA 2×RJ45 BusAdapter
BA 2×FC BusAdapter
BA 2×LC BusAdapter
BA 2xSCRJ BusAdapter
BA SCRJ/RJ45 BusAdapter
BA SCRJ/FC BusAdapter
BA LC/RJ45 BusAdapter
BA LC/FC BusAdapter
Strain relief for PROFINET cable
24 V DC connector (one included in the scope of delivery)
Labeling strips
Reference identification label
Information on the BusAdapters is available in the BusAdapter
(https://support.industry.siemens.com/cs/ww/en/view/109751716) manual.
You can find more information on accessories in the ET 200SP distributed I/O system
(http://support.automation.siemens.com/WW/view/en/58649293) system manual.
Server module
The server module is included in the scope of delivery of the interface module and available
separately as an accessory.