Interrupts/diagnostic messages 
  6.1 Status and error displays 
Technology module TM ECC 2xPWM ST (6FE1242-6TM10-0BB1) 
Manual, 04/2018, A5E42681298B-AA 
49 
 
Charging outlet state (enable) 
 
Charging outlet 0 (EN0) or charging outlet 1 (EN1) disabled. 
The corresponding VS0/VS1-LED and error LED F0/F1 is also off in this case. 
 
Charging outlet 0 (EN0) or charging outlet 1 (EN1) enabled. 
 
flashes, 
Charging outlet 0 (EN0) or charging outlet 1 (EN1) blocked by user program.  
 
flashes, 
Communications fault for charging outlet 0 (EN0) or charging outlet 1 (EN1).  
CPU is in STOP or the PIQ valid bit is not set. 
 
 
 
Off 
No vehicle is connected to the charging station. 
(State "A") if no error is pending (see LED F0/F1)  
(State "F") if error is pending (see LED F0/F1) 
 
A vehicle is connected to the charging station and ready for charging. 
 
flashes, 
1 Hz  
Vehicle charging  
(State "C") 
 
flashes, 
Vehicle charging, ventilation required  
(State "D") 
 
Contactor for charging outlet 0 (DQ0) or charging outlet 1 (DQ1) not controlled. 
 
 
On 
Contactor for charging outlet 0 (DQ0) or charging outlet 1 (DQ1) not controlled. 
(This is not a functional check for the corresponding contactor; it only shows whether it is 
activated. Only readback of the affected feedback input provides certainty.) 
 
Status of the feedback input for charging outlet 0 (DI0) or charging outlet 1 (DI1)  
 
Status of the feedback input for charging outlet 0 (DI0) or charging outlet 1 (DI1)  
 
Off 
Status of connector locking for charging outlet 0 (A0) or charging outlet 1 (A1) 
"Connector unlocked" or no locking active 
(If no feedback is configured with GSDML or HSP, this LED always stays "off") 
 
Status of connector locking for charging outlet 0 (A0) or charging outlet 1 (A1) 
"Connector locked"