EasyManua.ls Logo

Siemens SIMATIC HMI 177 - Page 50

Siemens SIMATIC HMI 177
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operator elements and displays
5.1 Mobile Panel
Mobile Panel 177 (WinCC flexible)
5-4 Operating Instructions (Compact), Edition 07/2005
Switch settings
The primary function of the evaluating logic is to recognize the three switch settings:
Switch setting Function Enable switch Switch state
1 Neutral position Not activated OFF (open)
2 Enable Activated ON (closed)
3 Panic Pressed OFF (open)
(6 (6 (6(QDEOHVZLWFK
 
Figure 5-3 Switch settings of enabling switch
When the enabling switch is activated, the following switch sequences are possible:
Normal activation
(6(QDEOHVZLWFK
1HXWUDOSRVLWLRQ
(6(6
6ZLWFKVHWWLQJ
(6(6
(QDEOH
1HXWUDOSRVLWLRQ
[\
[
\

Figure 5-4 Interlinking of switch settings for normal operation
Panic activation
If the operator has pressed the enabling switch through to the "Panic" setting, the "Enable"
setting will be skipped when the switch is released.
(6(QDEOHVZLWFK
1HXWUDOSRVLWLRQ
(6(6
6ZLWFKVHWWLQJ
(6(6
(QDEOH
3DQLF 1HXWUDOSRVLWLRQ
[X\
[X
\

Figure 5-5 Interlinking of switch settings for panic activation
The signals of the enabling switch are fed to the terminal box via the connecting cable. For
manual special operating modes, these signals must be interconnected from the terminal
box to the safety circuit using two channels for power interruption.

Table of Contents