EasyManua.ls Logo

Siemens SIMATIC Ident RF200 - Page 14

Siemens SIMATIC Ident RF200
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Command and message frames
2.5 SLG STATUS (mode 1) command
ASCII protocol for RF200
14 Operating Manual, 11/2016, C79000-G8976-C329-04
Address
Designation
Value
Description
Byte 9 0xXX XX = 31 RF260R
XX = 32 RF210R / RF220R
XX = 33 RF240R
XX = 34 RF240R (RS-232)
XX = 35 RF260R (RS-232)
XX = 36 RF250R
XX = 37 RF250R (RS-232)
Bytes 10..11
HW-V(low)
0x30, 0x31
RF200 family
Bytes 12..13
HW-V(high)
0x30, 0x30
Reserved
Byte 14
Url-V
xx, high nibble
--
Byte 15
xx, low nibble
Byte 16
yy, high nibble
Byte 17
yy, low nibble
Byte 18
FW
0x33
FW variant RF200 ISO only
Byte 19
0x33
Byte 20
FW-V
xx, high nibble
Firmware version, format xx.yy
Byte 21
xx, low nibble
Byte 22
yy, high nibble
Byte 23
yy, low nibble
Byte 24
TR
0x33
Driver variant LAUF
Byte 25 0x33
Byte 26
TR-V
xx, high nibble
Version of the driver, format xx.yy
Byte 27
xx, low nibble
Byte 28
yy, high nibble
Byte 29
yy, low nibble
Byte 30
SS
0x30
0x31 RS-422 interface
0x32 RS-232 interface
Byte 31
0x31 / 0x32
Byte 32
Baud rate
0x30
0x31 19.2 kBd
0x33 57.6 kBd
0x35 115.2 kBd
Byte 33 0x31 / 0x33 / 0x35
Byte 34
Interface parameters
0x30
Bit 0: 0 1 stop bit; 1 2 stop bits
Bit 1: 0 8 data bits
Bit 2, 3: 00 odd parity;
01 even parity;
10 no parity
Byte 35 0x3X
Bytes 36..39
Reserved
0x30
--
Byte 40
LTBG
0x30
Reserved
Byte 41
0x30
Byte 42
MTAG
0x30
Number of transponders that can
be processed
Byte 43
0x31
Bytes 44..45
Reserved
0x30
--

Related product manuals