Scan mode function extension for ASCII readers
3.3 Communication in scan mode
ASCII protocol for RF200
30 Operating Manual, 11/2016, C79000-G8976-C329-04
All parameters must always be transmitted together. If the reader configuration is not saved
on the host, you should first read out the parameters saved to the reader.
3.3.2
Read statusframe
This frame allows you to read out the reader status. This includes the parameters and
version information. You can identify individual readers by the version information. This
information is specified at factory and cannot be changed.
After the acknowledgement is sent, the reader switches automatically back to read data
mode.
Table 3- 13 Read statusframe
Command parameter
Frame parameter
Byte 1
Byte 2
Byte 3
Byte 1
...
Byte 21
BCC
Command Status Count Para ... Para
0x02
0x00
0x15
0x00
...
0x00
Table 3- 14 Read statusframe (retentive)
Command parameter
Frame parameter
Byte 1 Byte 2 Byte 3 Byte 1 ... Byte 21 BCC
Command
Status
Count
Para
...
Para
0x02
0x01
0x15
0x00
...
0x00
Table 3- 15 Read statusframe acknowledgment
Command
Error code
Count
Byte 1
...
Byte 25
BCC
0x01
0xXX
0x19
Para
...
Para