Properties
Interface module IM151-1 STANDARD (6ES7151-1AA06-0AB0)
10 Manual, 07/2015, A5E01075950-AD
• Reverse polarity protection
Yes
• Voltage failure backup
Min. 20 ms
• Between backplane bus and electronics
No
• Between PROFIBUS DP and electronics
Yes
• Between supply voltage and electronics
No
Permissible potential difference (to mounting rail)
Current consumption from rated supply voltage
Approx. 200 mA
Status, interrupts, diagnostics
• Group error
Red "SF" LED
• PROFIBUS DP bus monitoring
Red "BF" LED
• Monitoring of the power supply voltage of the
electronics
Green "ON" LED
Updating the firmware of the IM151-1 STANDARD
The IM151-1 STANDARD firmware can be updated starting with
STEP 7
V5.1, SP 3 (via
accessible nodes).
To update the firmware, you receive files (*.UPD) with the current firmware.
The following requirements must be met:
● The IM151-1 STANDARD in the station whose firmware is to be updated must be
accessible online.
● The files with the current firmware version must be available in the file system of your
programming device or PC.
You can find information on this procedure in the
STEP 7
online help.
Note
Make sure that the correct firmware version for the interface module
in question is used for
the update. An interface module with an older order number cannot be updated with the
firmware version for an interface module with a more recent order number and vice versa.