Operator controls and operating modes of the CPU 410-5H
7.4 Performing a memory reset
CPU 410-5H Process Automation
120 System Manual, 09/2014, A5E31622160-AB
7.4
Performing a memory reset
Memory reset process in the CPU
You can perform a memory reset of the CPU from the programming device. During a
memory reset, the following process occurs on the CPU:
The CPU deletes the entire user program in the main memory.
The CPU deletes the user program from the load memory.
The CPU deletes all counters, bit memories, and timers, but not the time of day.
The CPU tests its hardware.
The CPU sets its parameters to default settings.
The LEDs behave as following during the memory reset:
1. The STOP LED flashes for about 1-2 seconds at 2 Hz.
2. All LEDs light up for approximately 10 seconds.
3. The STOP LED flashes for about 40 seconds at 2 Hz.
4. The STOP LED lights up permanently.
Data retained after a memory reset...
The following values are retained after a memory reset:
The content of the diagnostic buffer
The baud rate of the DP interface
The parameters of the PN interfaces
Name (NameOfStation)
IP address of CPU
Subnet mask
Static SNMP parameters
The time of day
The status and value of the operating hours counter