EasyManua.ls Logo

Siemens SIMATIC PCS 7 CPU 410-5H

Siemens SIMATIC PCS 7 CPU 410-5H
380 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Introduction to CPU 410-5H
2.4 The basic system for redundant operation
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB
27
2.4
The basic system for redundant operation
Hardware of the basic system
The basic system consists of the hardware components required for a fault-tolerant
controller. The following figure shows the components in the configuration.
The basic system can be expanded with standard modules of the S7-400. There are
restrictions for the function modules and communication processors. See Appendix Function
and communication modules that can be used in a redundant configuration (Page 335).
Figure 2-3 Hardware of the S7-400H basic system
Central processing units
The two CPUs are the heart of the S7-400H. Use the switch
on the rear
of the CPU to set
the rack numbers. In the following sections, we will refer to the CPU in rack 0 as CPU 0, and
to the CPU in rack 1 as CPU 1.
Rack for S7-400H
The UR2-H rack supports the installation of two separate subsystems with nine slots each,
and is suitable for installation in 19" cabinets.
You can also set up the S7-400H in two separate racks. The racks UR1, UR2, and CR3 are
available for this purpose.

Table of Contents

Related product manuals