Special functions of the CPU 410-5H
9.1 Security levels
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB
139
Additional aspects
Both fault-tolerant CPUs of a fault-tolerant system can have different protection levels in
STOP.
The protection level is transferred from the master to the standby during link-up/update
operations.
The set protection levels of both fault-tolerant CPUs are retained if you make
modifications to the plant during operation.
The protection level is transferred to the target CPU in the following cases:
Switch to CPU with modified configuration
Switching to a CPU with modified PO limit
Switching to a CPU with modified operating system
Switching to a CPU using only one intact redundant link