Loading...
Synchronization modules
12.2 Installation of fiber-optic cables
CPU 410-5H Process Automation
208 System Manual, 09/2014, A5E31622160-AB
Cable pull-in
Note the points below when pulling-in fiber-optic cables:
Always observe the information on pull forces in the data sheet of the corresponding
fiber-optic cable.
Do not reel off any greater lengths when you pull in the cables.
Install the fiber-optic cable directly from the cable drum wherever possible.
Do not spool the fiber-optic cable sideways off the drum flange (risk of twisting).
You should use a cable pulling sleeve to pull in the fiber-optic cable.
Always observe the specified bending radii.
Do not use any grease or oil-based lubricants.
You may use the lubricants listed below to support the pulling-in of fiber-optic cables.
Yellow compound (Wire-Pulling, lubricant from Klein Tools; 51000)
Soft soap
Dishwashing liquid
Talcum powder
Detergent
Pressure
Do not exert any pressure on the cable, for example, by the inappropriate use of clamps
(cable quick-mount) or cable ties. Your installation should also prevent anyone from stepping
onto the cable.
Influence of heat
Fiber-optic cables are highly sensitive to direct heat, which means the cables must not be
worked on using hot-air guns or gas burners as used in heat-shrink tubing technology.