Supplementary information
15.3 System status lists for PROFINET IO
CPU 410-5H Process Automation
236 System Manual, 09/2014, A5E31622160-AB
SSL-ID
PROFINET IO
PROFIBUS DP
Applicability
W#16#0D91 Yes
Parameter adr1 changed
No, external interface
Yes Module status information of all modules
in the specified rack/station
W#16#xy92 No
Replacement: SSL-ID
W#16#0x94
Yes Rack/station status information
Replace this system status list with the
system status list with ID W#16#xy94 in
PROFIBUS DP, as well.
W#16#0x94 Yes, internal interface
No, external interface
Yes, internal interface
No, external interface
Rack/station status information
W#16#0C96 Yes, internal interface
No, external interface
Yes, internal interface
No, external interface
Module status information of a submod-
ule using the logical address of this sub-
module
W#16#0591 Yes
Parameter adr1 changed
Yes Module status information for the inter-
faces of a module
W#16#0696 Yes, internal interface
No, external interface
No Module status information of all submod-
ules on an internal interface of a module
using the logical address of the module,
not possible for submodule 0 (= module)
Detailed information
For detailed descriptions of the individual system status lists, refer to Manual
System
Software for S7-300/400 System and Standard Functions
.