Connection examples for redundant I/Os
C.2 Interconnection of output modules
CPU 410-5H Process Automation
338 System Manual, 09/2014, A5E31622160-AB
Information on connecting digital output modules via diodes
Suitable diodes are diodes with U
_r
>=200 V and I_
F
>= 1 A (e.g., types from the series
1N4003 ... 1N4007).
It is advisable to separate the ground of the module and the ground of the load. There
must be equipotential bonding between both.
Information on connecting analog output modules via diodes
Suitable diodes are diodes with U
_r
>=200 V and I_
F
>= 1 A (e.g., types from the series
1N4003 ... 1N4007).
A separate load supply is advisable. There must be equipotential bonding between both
load supplies.