Cycle and reaction times
5.5 Interrupt response time
CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05
5-23
Process interrupt processing
Process interrupt processing begins after process interrupt OB40 is called. Higher-priority
interrupts stop process interrupt processing. Direct I/O access is executed during runtime of
the instruction. After process interrupt processing has terminated, cyclic program execution
continues or further interrupt OBs of equal or lower priority are called and processed.
See also
Overview (Page 5-1)
5.5.2 Reproducibility of delay interrupts and watchdog interrupts
Definition of "Reproducibility"
Delay interrupt:
The period that expires between the call of the first instruction in the interrupt OB and the
programmed time of interrupt.
Watchdog interrupt:
The fluctuation width of the interval between two successive calls, measured between the
respective initial instructions of the interrupt OBs.
Reproducibility
The following times apply for the CPUs described in this manual:
Delay interrupt: +/- 200 μs
Watchdog interrupt: +/- 200 μs
These times only apply if the interrupt can actually be executed at this time and if not
interrupted, for example, by higher-priority interrupts or queued interrupts of equal priority.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals