Communication
3.2 Communication services
CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05
3-9
3.2.6 Global data communication (MPI only)
Properties
Global data communication is used for cyclic exchange of global data via MPI subnets (for
example, I, Q, M) between SIMATIC S7 CPUs (data exchange without acknowledgement).
One CPU broadcasts its data to all other DP CPUs on the MPI subnet. This function is
integrated in the CPU operating system.
Reduction ratio
The reduction ratio specifies the cyclic intervals for GD communication. You can set the
reduction ratio when you configure global data communication in STEP 7. For example, if
you set a reduction ratio of 7, global data are transferred only with every 7th cycle. This
reduces CPU load.
Send and receive conditions
Conditions which should be satisfied for GD communication:
For the transmitter of a GD packet:
Reduction ratio
transmitter
x cycle time
transmitter
≥ 60 ms
For the receiver of a GD packet:
Reduction ratio
receiver
x cycle time
receiver
< reduction ratio
transmitter
x cycle time
transmitter
A GD packet may be lost if you do not adhere to these conditions. The reasons being:
the performance of the "smallest" CPU in the GD circuit
asynchronous transmitting / receiving of global data at the stations
When setting in STEP 7: “Transmit after each CPU cycle“, and the CPU has a short scan
cycle time (< 60 ms), the operating system might overwrite a GD packet of the CPU before it
is transmitted. The loss of global data is indicated in the status box of a GD circuit, if you set
this function in your STEP 7 configuration.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals