Cycle and reaction times
5.6 Sample calculations
CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05
5-25
Calculating the longest response time
Longest response time:
6.8 ms x 2 = 13.6 ms.
I/O delay can be neglected.
Neither PROFIBUS DP, nor PROFINET IO are being used, so you do not have to make
allowances for any DP cycle times on PROFIBUS DP or for PROFINET IO update times.
Interrupts are not processed.
5.6.2 Sample of response time calculation
Installation
You have configured an S7300 and equipped it with the following modules in two racks:
a CPU 314C-2
Configuring the cycle load as a result of communication: 40 %
4 digital input modules SM 321; DI 32 x 24 VDC (4 bytes each in the PI)
3 digital output modules SM 322; DO 16 x 24 VDC/0.5 A (2 bytes each in the PI)
2 analog input modules SM 331; AI 8 x 12-bit (not in the PI)
2 analog output modules SM 332; AO 4 x 12 bit (not in the PI)
User program
According to the instruction list, the user program runtime is 10.0 ms.
Calculating the cycle time
In this example, the cycle time is equivalent to the sum of the following times:
User program execution time:
approx. 10 ms x CPU-specific factor 1.10 = approx. 11 ms
Process image transfer time
Process image of inputs: 100 μs + 16 bytes x 37 μs = approx. 0.7 ms
Process image of outputs: 100 μs + 6 bytes x 37 μs = approx. 0.3 ms
Operating system runtime at the scan cycle checkpoint:
approx. 0.5 ms
The sum of the listed times is equivalent to the cycle time:
Cycle time = 11.0 ms + 0.7 ms + 0.3 ms + 0.5 ms = 12.5 ms.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals