Commissioning
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
8-25
DP address areas of the CPUs
Table 8-7 DP address areas of the CPUs
Address area 315-2 DP
313C-2 DP
314C-2 DP
316-2 DP 318-2 DP
DP address area
for I/Os
1024 bytes 2048 bytes 8192 bytes
Number of those in the I/O
process image
Bytes 0 to 127 Bytes 0 to 127 Byte 0 to 255 (default),
configurable up to
byte 2047
DP diagnostic addresses occupy 1 byte per DP master and DP slave in the input
address area. For example, at these addresses DP standard diagnostics can be
called for the respective node ( LADDR parameter of SFC13). The DP diagnostic
addresses are specified in your configuration. If you do not specify any DP
diagnostic addresses, 7 STEP 7 assigns these DP diagnostic addresses, starting
at the highest byte address downwards .
With CPU 31xC-2DP as master/ CPUx>=3 as master with DPV1 configuration you
assign two different diagnostic addresses to S7 slaves:
Diagnostic address of the slave (address for slot 0)
At this address all slave events are reported in the DP master (station
representative), e.g. station failure.
Diagnostic address of the module (address for slot 2)
At this address all module (e.g. CPU 313C-2 DP as I-Slave) events are reported
in the master (OB82). With a CPU as DP-Slave, for example, diagnostic
interrupts for operating mode transitions are reported at this address.