Commissioning
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
8-29
8.7.3 Commissioning the CPU as DP slave
Prerequisites for commissioning
The DP master is configured and programmed.
If the MPI/DP interface of CPU 318-2 DP is to be operated as DP interface, you must
configure the interface accordingly.
You must program and configure CPU 31x-2 DP/31xC-2 DP as DP slave prior to
commissioning. That is, in STEP 7 you must:
"switch on" the CPU as DP slave,
assign a PROFIBUS address to the CPU,
assign a slave diagnostic address to the CPU,
specify whether the DP master is an S7 DP master or another DP master,
specify the address areas for data exchange with the DP master.
All other DP slaves are programmed and configured.
GSD Files
When working on an IM 308-C or non-Siemens system, you require a GSD file in
order to be able to configure CPU 31x-2 DP/31xC-2 DP as DP slave in a DP
master system.
COM PROFIBUS as of V 4.0 includes this GSD file.
When working with an older version or another configuration tool, you can
download the GSD file under:
Internet URL http://www.ad.siemens.de/csi/gsd
or
via modem from the SSC (Interface Center) Fürth, Germany; Phone number (0911)
911/737972
Configuration and parameter assignment message frame
STEP 7 supports you in configuring/programming CPU 31x-2 DP/31xC-2 DP.
Should you require a description of the configuration and parameter assignment
frame, in order to use a bus monitor for example, you can find it on the Internet at
http://www.ad.siemens.de/csinfo under article ID 1452338.