EasyManua.ls Logo

Siemens Simatic S7-300 - Cable Routing Inside Buildings

Siemens Simatic S7-300
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
S7-300 Programmable Controller Hardware and Installation
11-14 A5E00105492-01
The lower the impedance of an equipotential conductor, the more effective is
equipotential bonding.
When shielded signal cables interconnect two system components and the
shielding is connected on both ends to ground/protective conductors, the
impedance of the additionally installed equipotential conductor must not exceed
10% of the shielding impedance.
The cross-sectional dimension of an equipotential conductor must be sufficient
to handle the maximum equipotential current flow. Practical and proven
equipotential conductor cross-section is 16 mm
2
.
Always use equipotential conductors made of copper or galvanized steel.
Always connect the cables on a large surface to the equipotential
busbar/protective conductor and protect it against corrosion.
Route your equipotential conductor to minimize the area between the
equipotential conductor and signal lines as far as possible (see the figure
below).
Figure 11-5 Equipotential bonding
11.2.7 Cable routing inside buildings
Introduction
Inside buildings (inside and outside cabinets), clearances must be maintained
between groups of different cables to achieve the necessary electromagnetic

Table of Contents

Other manuals for Siemens Simatic S7-300

Related product manuals