EasyManua.ls Logo

Siemens Simatic S7-300 - Marginal Conditions for Wiring Interior Bus Cables

Siemens Simatic S7-300
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuring
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
4-35
The table below lists the properties of these bus cables.
Table 4-16 Properties of PROFIBUS cables
Properties Values
Impedance level approx. 135 to 160 (f = 3 MHz to 20 MHz)
Loop resistance 115 /km
Effective capacitance 30 nF/km
Attenuation 0.9 dB/100 m (f = 200 kHz)
Permissible conductor cross-sections 0.3 mm
2
to 0.5 mm
2
Permissible cable diameter 8 mm ± 0.5 mm
Wiring bus cables
When wiring PROFIBUS cables, you must not
twist,
stretch
or compress them.
When wiring indoor bus cables, also maintain the following marginal conditions
(d
A
= outer cable diameter):
Table 4-17 Marginal conditions for wiring interior bus cables
Characteristics Condition
Bending radius (one-off) 80 mm (10 x d
A
)
Bending radius (multiple times) 160 mm (20 x d
A
)
Permissible temperature range during installation –5 °C to +50 °C
Shelf and stationary operating temperature range –30 °C to +65 °C
Cross-reference
If you want to use optical waveguide cables for PROFIBUS, you can find further
information on this topic in the Manual SIMATIC NET, PROFIBUS Networks.

Table of Contents

Other manuals for Siemens Simatic S7-300