EasyManua.ls Logo

Siemens Simatic S7-300 - Isolated or Non-Isolated Modules

Siemens Simatic S7-300
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuring
S7-300 Programmable Controller Hardware and Installation
4-18 A5E00105492-01
4.8.4 Isolated or non-isolated modules?
Isolated modules
In configurations with isolated modules, the reference potentials of the control
circuit (M
internal
) and load circuit (M
external
) are electrically isolated (see Figure).
Application
Use isolated modules for:
All AC load circuits
DC load circuits with separate reference potential
Examples:
DC load circuits whose sensors have different reference potentials (for
example if grounded sensors are located at some considerable distance
from the control system and no equipotential bonding is possible)
DC load circuits with grounded positive pole (L+) (battery circuits).
Isolated modules and grounding conception
You can use isolated modules, regardless of whether or not the control system's
reference potential is grounded.
Example:
The figure below shows a sample configuration: One CPU 31xC or 312 IFM with
isolated modules.

Table of Contents

Other manuals for Siemens Simatic S7-300

Related product manuals