Use grounded, spiraled, current-conducting metal straps or metal braiding as a
cable shield at both ends, for example, NYCY or A2Y(K)Y.
Install cables in one of the following media:
in continuous metal pipes that are grounded at both ends, or
in continuously armored concrete ducts or
on closed metal cable trays grounded at both ends.
Use optical waveguides instead of metal conductors.
Additional Measures
If you cannot take measures as described above, you must install a high-voltage
protection for your system between the 0 <-> 1 transition points with a lightning
conductor. The table below contains the components you can use for high-voltage
protection of your plant.