Parameter assignment / addressing   
5.6 Configuring PROFINET IO 
  SIMOTION D4x5-2 
150  Commissioning and Hardware Installation Manual, 02/2012 
●  An F-CPU can only be connected to one of the two PROFINET interfaces, because fail-
safe I/O transfer areas can only be configured either on the I device on the onboard 
PROFINET interface or on the CBE30-2. 
The PROFIsafe message frames are routed to the following drives: 
–  Drives on the SINAMICS Integrated and CX32-2 
–  Drives on the onboard PROFINET interface (X150 interface) 
–  Drives on the CBE30-2 (X1400 interface) 
The maximum quantity structure for PROFIsafe on PROFINET is therefore not increased 
by using a second PROFINET interface. 
●  If Servo_fast is not used, the servo isochronous devices can be assigned to both 
PROFINET interfaces. 
●  A redundant sync master is not permitted in the SYNC domain of the onboard PROFINET 
interface if both PROFINET interfaces are operated isochronously and the CBE30-2 is 
configured as a sync slave or IRT I device. 
Rules for Servo_fast 
The following rules apply for the onboard PROFINET interface (X150) assigned to the 
Servo_fast:  
●  The interfaces are permanently assigned: 
–  Servo/IPO/IPO_2 to the CBE30-2 (or DP and DP Integrated) 
–  Servo_fast and IPO_fast to the onboard PROFINET interface 
●  If the Servo_fast is used, only one CACF (Controller Application Cycle Factor) = 1 is 
permitted for Servo and Servo_fast, i.e. it must be set: 
–  Servo cycle clock = send cycle clock of the PROFINET interface X1400 (CBE30-2) 
–  Servo_fast cycle clock = send cycle clock of the PROFINET interface X150 (onboard 
interface) 
●  The Servo_fast must have a reduction ratio to the Servo of 2, 4, 8, or 16. 
Additional information 
For further information, see the 
SIMOTION Communication
 System Manual.