Commissioning (software)   
6.5 Additional information on configuring the SINAMICS Integrated 
  SIMOTION D4x5-2 
220  Commissioning and Hardware Installation Manual, 02/2012 
If an error is detected during the execution of a parameter job, the error cause is signaled via 
the parameter itself (no message via the fault buffer).  
Causes of errors for parameter jobs  
Table 6- 7  Causes of errors of the parameter jobs 
Value  Cause 
10  Error occurred while deleting 
11  No backup possible: Memory card is not inserted 
12  No backup possible: Memory card is full 
13  Backup could not be completed (e.g. memory card removed during the backup) 
14  Restoration not possible: Memory card is not inserted 
15  Restoration not possible: Checksum of the NVRAM data backup file is faulty 
16  Restoration not possible: No backup available 
 
 
 
Note 
The memory card must be always remain inserted for SIMOTION D; please refer to the 
SINAMICS manuals for which SINAMICS control units allow the memory card to be 
removed. 
 
Parameter p7775 is only reset automatically to 0 after the successful completion of a job. 
Know-how and write protection 
●  Parameter p7775 is not part of the know-how protection.  
I.e. the parameter can be read and written irrespective of the know-how. 
●  Parameter p7775 is part of the write protection. This means the parameter can only be 
written by the controller that configured a PZD cyclic communication with the SINAMICS 
when write protection is activated (p7761 = 1). 
All other write jobs are acknowledged negatively, e.g. 
–  SCOUT/STARTER 
–  For SINAMICS CUs, BOP, IOP, AOP 
–  Other masters that only communicate acyclically with the SINAMICS