Commissioning via the built-in BOP
5.6 Function commissioning
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
107
Setting parameters
Parameter
Function
Setting
P1240[0...2] Configuration of Vdc controller This parameter enables/disables Vdc controller.
= 0: Vdc controller disabled
= 1: Vdc_max controller enabled (factory default)
= 2: Kinetic buffering (Vdc_min controller) enabled
= 3: Vdc_max controller and kinetic buffering (KIB) enabled
Note:
This parameter must be set to 0 (Vdc controller disa-
bled) if a braking resistor is used.
P0210 Supply voltage [V] This parameter defines the supply voltage. Its default value
depends upon the type of converter.
Range:
380 to 480 (for three phase AC 400 V converters)
200 to 240 (for single phase AC 230 V converters)