Commissioning via the built-in BOP
5.5 Quick commissioning
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
79
Application macro AP021 - Compressor applications
Converter running at a lower speed inhibited
P1312[0] Starting boost 0 30 Boost only effective when accelerating for the first time
Boost only effective when accelerating or braking
Additional boost over the complete frequency range
Ramp-up time from zero to maximum frequency
Ramp-down time from maximum frequency to zero
Application macro AP030 - Conveyor applications
P1312[0] Starting boost 0 30 Boost only effective when accelerating for the first time
Ramp-up time from zero to maximum frequency
Ramp-down time from maximum frequency to zero
5.5.1.5 Setting common parameters
Functionality
This menu provides some common parameters for converter performance optimization.
Text menu
If you set P8553 to 1, parameter numbers in this menu are replaced with short text.
Setting parameters
P1080[0] 1 Minimum motor
frequency
P1001[0] 2 Fixed frequency
setpoint 1
P1082[0] 1 Maximum motor
frequency
P1002[0] 2 Fixed frequency
setpoint 2