Commissioning via the built-in BOP
5.5 Quick commissioning
SINAMICS V20 Converter
78 Operating Instructions, 10/2019, A5E34559884-012
Setting application macros
Application macro AP010 - Simple pump applications
Parameter
Description
Factory
default
Default for
AP010
Remarks
P1080[0]
Minimum frequency
0
15
Converter running at a lower speed inhibited
P1300[0]
Control mode
0
7
Quadratic V/f
P1110[0] BI: Inhibit negative frequen-
cy setpoint
0 1 Reverse pump rotation inhibited
P1210[0]
Automatic restart
1
2
Restart after mains blackout
P1120[0]
Ramp-up time
10
10
Ramp-up time from zero to maximum frequency
P1121[0]
Ramp-down time
10
10
Ramp-down time from maximum frequency to zero
Application macro AP020 - Simple fan applications
Parameter
Description
Factory
default
Default for
AP020
Remarks
P1110[0] BI: Inhibit negative frequency
setpoint
0 1 Reverse fan rotation inhibited
P1300[0]
Control mode
0
7
Quadratic V/f
P1200[0] Flying start 0 2 Search for the speed of the running motor with a
heavy inertia load so that the motor runs up to the
setpoint
P1210[0]
Automatic restart
1
2
Restart after mains blackout
P1080[0]
Minimum frequency
0
20
Converter running at a lower speed inhibited
P1120[0]
Ramp-up time
10
10
Ramp-up time from zero to maximum frequency
P1121[0]
Ramp-down time
10
20
Ramp-down time from maximum frequency to zero