Commissioning via the built-in BOP
5.5 Quick commissioning
SINAMICS V20 Converter
78 Operating Instructions, 10/2019, A5E34559884-012
Setting application macros
Application macro AP010 - Simple pump applications
Converter running at a lower speed inhibited
P1110[0] BI: Inhibit negative frequen-
0 1 Reverse pump rotation inhibited
Restart after mains blackout
Ramp-up time from zero to maximum frequency
Ramp-down time from maximum frequency to zero
Application macro AP020 - Simple fan applications
P1110[0] BI: Inhibit negative frequency
0 1 Reverse fan rotation inhibited
P1200[0] Flying start 0 2 Search for the speed of the running motor with a
heavy inertia load so that the motor runs up to the
Restart after mains blackout
Converter running at a lower speed inhibited
Ramp-up time from zero to maximum frequency
Ramp-down time from maximum frequency to zero