Commissioning via the built-in BOP
5.6 Function commissioning
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
125
Setting parameters
Parameter
Function
Setting
P2365[0...2] Hibernation ena-
ble/disable
Select or disable the hibernation functionality.
= 0: Disabled
= 1: Frequency hibernation (the frequency setpoint as the wakeup trigger)
= 2: PID hibernation (the PID error as the wakeup trigger)
Range: 0 to 2 (factory default: 0)
P2366[0...2] Delay before stop-
ping motor [s]
With hibernation enabled, this parameter defines the delay before activating the hi-
bernation mode of the converter.
Range: 0 to 254 (factory default: 5)
P2367[0...2] Delay before starting
motor [s]
With hibernation enabled, this parameter defines the delay before "waking up" (disa-
bling) the hibernation mode of the converter.
Range: 0 to 254 (factory default: 2)
P2390 PID hibernation
setpoint [%]
When the value of P2365 is set to 2 and the converter under PID control drops below
the PID hibernation setpoint, the PID hibernation timer P2391 is started. When the
PID hibernation timer has expired, the converter is ramped down to stop and enters
the PID hibernation mode.
Range: -200.00 to 200.00 (factory default: 0)
P2391 PID hibernation timer
[s]
When the PID hibernation timer P2391 has expired, the converter is ramped down to
stop and enters the PID hibernation mode.
Range: 0 to 254 (factory default: 0)
P2392 PID hibernation
restart setpoint [%]
While in the PID hibernation mode, the PID controller continues to generate the error
r2273. Once this reaches the restart point P2392, the converter immediately ramps to
the setpoint calculated by the PID controller.
Range: -200.00 to 200.00 (factory default: 0)
r2399 CO/BO: PID hiberna-
tion status word
Displays the PID hibernation status word.
Bit 00: Not used
Bit 01: PID hibernation enabled (The PID hibernation mode is enabled and the con-
verter is not in the mode.)
Bit 02: Hibernation active (The PID hibernation mode is enabled and the converter is
in the mode.)
Factory default: 0
P1080[0...2] Minimum frequency
[Hz]
Sets minimum motor frequency at which motor will run irrespective of frequency set-
point. Value set here is valid both for clockwise and for counterclockwise rotation.
Range: 0.00 to 550.00 (factory default: 0.00)